How do we calculate?
In ASME B31.3 the hydrostatic test is 1.5 × design pressure and the pneumatic test 1.1 × design pressure. In EN 13480 the hydrostatic test is at least 1.43 × allowable pressure. In EN 12845 sprinkler systems are tested for 2 hours at 1.5 × maximum operating pressure (min. 15 bar). Flanges are compared with 1.5 × PN.
Let us turn your calculation into a bill of materials
Send us the list from the calculator; we will quote flanges, elbows, tees, reducers, pipes and valves in a single offer, with EN 10204 3.1 material certificates.
This calculator is used in these sectors: Building services (HVAC & plumbing). All calculators →
Results are for preliminary selection and do not replace engineering design. Ask our technical team for the final selection.