How do we calculate?
The specific volume of steam is taken from the saturated steam table; required inside diameter = √(4 × volumetric flow ÷ (π × velocity)). The fraction of condensate that flashes when it drops to atmospheric pressure = (hf − 419) ÷ 2257, and the return line is sized for this steam.
Let us turn your calculation into a bill of materials
Send us the list from the calculator; we will quote flanges, elbows, tees, reducers, pipes and valves in a single offer, with EN 10204 3.1 material certificates.
This calculator is used in these sectors: Refinery, Industrial manufacturing. All calculators →
Results are for preliminary selection and do not replace engineering design. Ask our technical team for the final selection.