Cold Water Pipe Sizing

Riser size from the number of flats and fixtures. Main and riser sizes (TS EN 806).

Calculating…
Yazıcı Endüstri · yaziciendustri.com.tr

How do we calculate?

EN 806-3 simplified method: the loading units (LU) of all fixtures are summed (washbasin and cistern 1, shower, sink and machines 2, bath 4, garden tap 5 LU; 1 LU = 0.1 L/s). According to the galvanized steel pipe table, DN15 carries at most 6 LU, DN20 16 LU, DN25 40 LU, DN32 160 LU, DN40 300 LU, DN50 600 LU, DN65 1600 LU; no single fixture larger than 4 LU is connected to DN15.

Let us turn your calculation into a bill of materials

Send us the list from the calculator; we will quote flanges, elbows, tees, reducers, pipes and valves in a single offer, with EN 10204 3.1 material certificates.

This calculator is used in these sectors: Building services (HVAC & plumbing). All calculators →

Results are for preliminary selection and do not replace engineering design. Ask our technical team for the final selection.